How to interpret UHF partial discharge detector readings?

Hey there, if you’ve ever stared at a UHF partial discharge (PD) detector screen and thought, “What the heck do these squiggles and numbers even mean?”—you’re not alone. I work as part of the team behind the UHF PD detectors we build and sell, and I get this question every single week. Guys on the floor, field techs who just unboxed a unit, even seasoned maintenance guys who’ve been around transformers since before smartphones—all of them end up squinting at the readings at some point. Partial Discharge Detector

Let’s break this down like we’re grabbing a coffee and geeking out over electrical gear, no stuffy textbook jargon, no “here’s what Wikipedia says” garbage. First, quick UHF PD 101 for anyone who’s new to this: Partial discharge is that tiny, random electrical “leak” that happens inside high-voltage gear—think transformers, switchgear, cables, the whole nine yards. Most of the time, it’s harmless if caught early, but ignore it and you’re staring at a full-blown outage or even an equipment meltdown. UHF detectors work by picking up the radio waves those discharges give off (they sit between 300 MHz and 3 GHz, if you care, but just know they’re the high-frequency hum you can’t hear) instead of the old-school acoustic sensors that picked up sound vibrations. Way less noisy, way more accurate, if you know how to read the numbers.

First, let’s start with the basics you’ll see on every detector screen. The big number most people fixate on is the UHF signal magnitude—usually in millivolts (mV) or decibels (dBm), right? Wait, let’s be real: dBm is a log scale, so don’t overthink it. If your reading jumps from -50 dBm to -40 dBm, that’s 10x bigger, not a 10-point bump (I still see techs miscalculate this sometimes). But here’s the thing—magnitude alone is useless. I can’t tell you how many times a tech calls our support line panicking because their detector hit -35 dBm, then we walk them through and it’s just a bird landing on the switchgear bushing or a distant radio tower picking up stray frequency. That’s called background noise, and it’s the #1 mistake new users make: they don’t filter that out.

Next up: phase-resolved partial discharge (PRPD) patterns. This is the actual bread and butter of UHF PD readings, not just the magnitude number. Most modern detectors spit out a color-coded plot where the X and Y axes are AC voltage phase (like, 0 to 360 degrees, since power cycles at 50/60 Hz) and the brightness or size of the dots is the signal strength. There are three main patterns you need to memorize, and I’ll describe them like you’re seeing them on the screen:

  1. Positive/Negative Corona (aka “surface PD”): These are the big, blobby dots on the outer edges of the PRPD plot, right at the peak of the AC cycle’s positive and negative phases. Corona is usually from a loose connection, a dirty insulator, or a nicked wire on the outside of the gear—super common, super easy to fix. I see this all the time on old switchgear in warehouses; it’s usually a loose bolt that’s been vibrating for years.

  2. Internal Cavity Discharge: This is the spiky, symmetric pattern—two identical clusters of dots, one on the positive half, one on the negative half, right in the middle of the plot. This is the bad one. That means there’s a tiny air gap inside the insulation of the transformer or cable, and every time voltage hits that gap, it sparks. If you ignore this, that gap gets bigger, the spark gets stronger, and eventually the insulation blows. We had a customer last year who caught this with our detector before a scheduled outage—saved them $20k in emergency repairs and a week of downtime.

  3. Floating Electrode PD: This one looks like a messy, scattered cloud of dots all over the plot, no rhyme or reason. That’s when a metal part inside the gear is loose and floating, not grounded right, so it’s picking up voltage. Way trickier than corona, because it can be hard to find the exact location, but if you spot the scattered pattern, you know you’re dealing with a floating part, not a surface issue.

Now, how do you separate actual PD from background noise? That’s the next big hurdle. Let’s talk tricks we teach every user when they first get their detector: First, move around the gear. Real PD will get stronger (bigger magnitude, brighter dots) as you get closer to the spot. Noise—like radio signals from a nearby cell tower—will either get weaker or stay the same, no matter where you stand. Second, turn off non-essential equipment on the site (like other tools, radios, even the detector’s own screen brightness sometimes) to cut electrical interference. Third, check the phase of the signal. Real PD is locked to the AC cycle, so its PRPD pattern will repeat every phase. Noise? It won’t line up with the cycle at all—random, no symmetry.

Wait, let’s talk thresholds, too. Our detectors come with a basic threshold setting that flags anything above, say, -45 dBm, but here’s the thing: there’s no one-size-fits-all number. A small switchgear cabinet will have way lower background noise than a huge transformer yard, so you can’t compare your reading to a buddy’s reading at another site. The real rule of thumb is: if the pattern is consistent and getting worse over time, that’s the red flag. We track this for every customer that uses our data logging feature—you can save readings every month and watch if the magnitude is going up, or the PRPD dots are getting bigger. Last month, a power utility guy told us he noticed his monthly -42 dBm reading was up to -38 after 6 months, so he scheduled a shutdown to replace a section of cable—no meltdown, no lost revenue.

Another thing people miss: location mapping. UHF PD is directional, right? Our detectors have a little antenna that points to the source, so if the signal is strongest at the top of the transformer, the problem is near the top. We teach techs to do a “scan” of the entire gear, moving the antenna 6 inches at a time, marking where the signal spikes. I’ve seen guys spend hours guessing where a PD is, and then with our detector, it takes 10 minutes. That’s the magic of UHF vs. old acoustic stuff—acoustic is sound, so if there’s a pipe making noise, you can’t tell if it’s PD or the pipe, but UHF is high-frequency radio waves, way less interference from the gear itself.

Wait, let’s throw in a real quick pitfall I’ve seen: don’t confuse partial discharge with transient signals. Transients are those big, one-time spikes—like when a lightning strike hits the grid, or a breaker switches on. They’re not PD, they’re just temporary surges. How to tell? Transients don’t repeat with the AC phase. If the signal only pops up once, not every cycle, it’s a transient, not a problem. That’s a huge one—so many new users panic over a single spike and schedule an unnecessary shutdown, which costs time and money for no reason.

Let’s test this with a quick example, like a tech showing up to a 10-year-old switchgear cabinet in a manufacturing plant. First, he turns on the detector, scans the outside. He sees a small spike at -48 dBm, but the PRPD pattern is two symmetric clusters right at phase peaks—corona, probably. He walks closer, gets to the top right corner of the cabinet, and the reading jumps to -40 dBm, same corona pattern. He checks the bolts there, and sure enough, one’s loose, vibrated loose from factory vibrations over time. Tightens it, rescans—signal drops to -55 dBm, gone. No problem. That’s a win.

Contrast that with another example: a transformer in a substation. Tech scans, sees a scattered cloud of dots all over the PRPD plot, magnitude bouncing between -42 and -38 dBm. He moves around, signal is strongest on the side of the transformer, not at any bolts. That’s floating electrode PD, internal, so he logs the reading, schedules a shutdown, takes the side panel off, finds a loose ground wire inside, tightens it—signal clears. That’s the bad pattern, caught early.

Now, if you’re using our detectors, we pre-load a quick start guide with all this, plus a cheat sheet taped to the detector case that lists the three main patterns and what they mean. We also have that data logging app that syncs to your phone, so you can track readings over time and export them for your maintenance logs—no more scribbling numbers on a clipboard.

I get it, this can feel overwhelming at first. The numbers, the patterns, the jargon—It’s like learning a new language, but once you spot that symmetric cluster or know that scattered cloud means trouble, it’s second nature. You start seeing PD patterns in everything, not just when you’re on the job.

If you’re still confused, or you’ve got a detector at work and can’t figure out what your readings are saying, hit us up. We work with field techs, maintenance managers, industrial electricians—everyone. We can walk you through a demo, answer questions, or help you calibrate your detector to your specific site. Partial discharge doesn’t have to be a mystery, and your equipment doesn’t have to be at risk because you don’t know how to read the numbers.

SF6 Comprehensive Analyzer References:

  1. IEC 60270, High-Voltage Test Techniques – Partial Discharge Measurements
  2. The Journal of Electrical Insulation and Dielectric Phenomena, "UHF Partial Discharge Detection for Rotating Machinery"
  3. IEEE Transactions on Power Delivery, "Interpretation of Phase-Resolved Partial Discharge Patterns in High-Voltage Equipment"

Wuhan Goldhome Hipot Electrical Co., Ltd.
Wuhan Goldhome Hipot Electrical Co., Ltd. is one of the most professional partial discharge detector manufacturers and suppliers in China, featured by quality products and good price. Welcome to buy partial discharge detector in stock here and get pricelist from our factory. Contact us for customized service.